ASP QUALIFICATION PROCESS
|
UPS technology |
| Trends - UPS technology |
| |
|
|
| |
(1) Optimized power
- Server/computer load are increasingly demanding more active power - high input Power Factor (PF)
(2) High efficiency
- Operating cost of UPS is important
(3) 99.999% availability
- Business continuity is supported by the availability of 7/24 power.
(4) THD
- UPS must not affect other consumers in the utility side or cause oversizing of gensets.
|
Trends - UPS technology |
| Load power factor vs. UPS rating |
| |
|
|
| |
| Let’s study three 100kVA UPS’s with 3 different output p.f. rating and try to size the acceptable IT load based on kW |
| |
|
|
|
| UPS |
A |
B |
C |
| utput p.f. |
0.9 |
0.8 |
1.0 |
| rated output kVA/kW |
100/90 |
100/80 |
100/100 |
| |
|
|
|
| Can the UPS |
YES |
NO |
YES |
| supply if the load |
|
short of |
|
| is 90 kW ? |
|
kW |
|
| |
|
|
|
| f load is 90 kW, p.f. 0.9 the needed current is based on apparent load of 90 kW / 0.9= 100 kVA |
| |
|
|
|
| A and C type of UPS can supply the same load! |
| Output pf. 0.9 should be requested from UPS suppliers! |
|
|
| Savings calculation |
| |
|
|
| |
Example, 8% better efficiency at 9 kW load:
8%*9kW*24h*365d = 6307 kW/h per year
Electricity cost:
6 Rupee / 1 kWh in India
Savings in electricity:
6*6307 = 37842 Rupee per year
+ 20% electric bill for air cooling/ventilation
>> Total savings Rs. 45,410 per year <<
Or Rs. 2,27,052 in 5 years.
|